1. The detector can be addressed in field by using Hand Held Programmer, easy and reliable for commissioning.
2. Single chip uses real-time sampling and data processing system.
3. Temperature and humidity drift compensation, dust accumulation degree and fault detection function.
4. Self-diagnostic function.
5. Non-polarized signal 2-wire.
6.LPCB CERTIFIED
Technical Specifications
1. Operating voltage
Rated voltage: DC24V Range allowed DC18V~DC28V
2. Operating current
Standby current: ≤ 0.3mA Alarm current: ≤ 0.9mA
3. Indicator
Red. Flashes when polling and illuminates in alarming.
4. Programming method
Electronically programming (encoding range: 1~255).
5. Monitoring protection area
The space height is 6~12 meters: 80m2
The space height is lower than 6 meters: 60m2
6. Wiring
Non-polarized signal 2-wire
7. Operating environment
Temperature: -10°C~+55°C
Relative Humidity: ≤95%, non-condensing
8. Dimension
Diameter: 100mm Height: 51mm (with base)
9. Ingress protection rating: IP23
10. Material and color of enclosure: ABS; milky white
11. Weight: about 110g
12. Mounting hole distance: 60mm
13. Standard: EN 54-29:2015

Emergency Start/Abort Button

Manual Call Point

Loop Extender

Conventional manual call point

Fire alarm control panel

Addressable Heat Fire Detector

Emergency Broadcasting Fire Telephone

Gas Fire-extinguishing Control Panel

Intelligent Addressable Sounder Strobe

Conventional heat detector

Detector Remote Indicator

Addressable Manual Call Point

Addressable Sounder visual indicator

Intelligent Fire Alarm Control Panel

Addressable heat detector

Conventional fire alarm control panel

Addressable Photoelectric Smoke Detector

Gas Extinguishing Indicator

Fire alarm control panel

Aspirating Smoke Detector